Solect Energy

MEGGER CALCULATOR

Enter values in the displays. Choose the correction table below.

MΩ

Insulation resistance · MΩ

°F

Cable temperature

ft

Tested cable length

FINAL RESULT

— MΩ

Enter the reading, temperature and cable length.

Normalized to 1,000 ft and the selected reference temperature.
A corrected value alone does not establish pass/fail.

View correction table and calculation

Cable temperature (°F)Correction factor

Corrected MΩ = measured MΩ × cable length (ft) ÷ 1,000 × temperature correction factor.

Between listed temperatures: linear interpolation. Outside the selected table range: no result.

Table values reproduced from the supplied Megger Calculator workbook. Source identified in the workbook: Megger Test guide.pdf, Rev01 Nov 2026, sections 5.1–5.2.